Butterfly Valves Fire Protection

Butterfly Valves for Fire Protection: UL, ULC and FM Listed UVB-G310

ValveAtlas supplies UL Listed, ULC Listed and FM Approved butterfly valves for fire protection service on sprinkler risers, standpipe zones, fire pump discharge, underground water mains and zone isolation. The UVB-G310 grooved-end butterfly valve with integrated supervisory tamper switch is the workhorse sprinkler-zone isolation valve on projects from Toronto high-rise to London data centre to New York commercial office.

This page is the technical reference for specifying engineers, EPC project firms, construction firms and mechanical subcontractors selecting butterfly valves on fire protection systems governed by NFPA 13, NFPA 20, NFPA 24, BS EN 12845, Approved Document B, Code du Québec Chapitre Bâtiment and the NYC Mechanical Code.

Butterfly valve range stocked at ValveAtlas

SKU Type End connection Pressure class Listings Sizes
UVB-G310 Grooved butterfly, gear operator, tamper switch AWWA/NPS grooved 300 psi CWP UL, ULC, FM 2″ to 12″
UVB-W310 Wafer butterfly, gear operator, tamper switch Wafer (pin-between-flange) 300 psi CWP UL, ULC, FM 2″ to 12″
UVB-L310 Lug butterfly, gear operator, tamper switch Lug (flanged-end service) 300 psi CWP UL, ULC, FM 2″ to 12″

Where butterfly valves are used in fire protection

Sprinkler zone isolation. NFPA 13 and BS EN 12845 require a listed indicating valve upstream of every sprinkler zone so the zone can be isolated for maintenance without shutting down the entire system. The UVB-G310 with integrated tamper switch satisfies both the indicating valve requirement (open/close visible at the gear operator) and the supervision requirement (tamper switch wired to the fire alarm control panel per NFPA 72).

Fire pump discharge isolation. NFPA 20 requires a listed indicating gate or butterfly valve on the system side of the pump discharge check valve. Butterfly valves do not belong on the suction side: NFPA 20 calls for a listed OS&Y gate valve in the suction pipe and permits no other type of control valve within 50 ft (15 m) of the pump suction flange. For horizontal split case and vertical turbine pumps discharging at 175 to 250 psi, the UVB-G310 300 psi CWP rating covers the service. For high-rise fire pumps discharging at 500 psi (tall-building standpipe pressure zones), ValveAtlas coordinates the 500 psi-class butterfly valve variant on special order.

Standpipe zone control. NFPA 14 and BS 9990 require isolation on each standpipe zone. The UVB-G310 is the standard selection on Class I, Class II and Class III standpipe zones across commercial high-rise and residential high-rise.

Underground water main tie-ins. NFPA 24 and AWWA M-class water main service use listed butterfly valves at the property-line tap, at the sprinkler riser base and at isolation points along the underground loop. UVB-G310 covers the service down to 2″ and up to 12″ in grooved-end configuration.

Listings and code acceptance

UL 1091. UVB-G310 carries UL 1091 (butterfly valves for fire protection service) listing. The UL certificate is issued to the manufacturer and is provided in the ValveAtlas submittal package.

ULC listing for Canadian projects. The ULC listing covers the same SKU under ANSI/CAN/UL/ULC 1091. Quebec RBQ projects, Ontario projects under the OBC and Canadian projects referencing NFPA 13 accept the ULC certificate.

FM Approval. FM Approvals Class 1112 (indicating valves for fire protection) certifies UVB-G310 for FM-insured properties under FM Global Data Sheet 2-0. Insurance surveyors at FM Global and other property insurers accept the FM certificate on their insured properties.

LPCB and UK acceptance. Where a UK specification or insurer requires LPCB-approved indicating valves under BS EN 12845 and the LPC Rules, confirm acceptance of UL/FM-listed valves with the insurance surveyor before ordering.

Approved-equal submittals

Where a specification names a specific manufacturer, we prepare an approved-equal submittal package (listing certificates, dimensional drawings and material data) for review by the engineer of record and the authority having jurisdiction.

Regional stock and delivery across the ValveAtlas network

Toronto. UVB-G310 2″ to 8″ in stock at Toronto HQ for same-day shipment across Ontario. See Fire Protection Toronto.

Montreal. Next-day truck freight from Toronto covers Montreal, Laval, Longueuil and the wider Quebec market. RBQ submittals include ULC certificate on UVB-G310. See Fire Protection Montreal.

New York. 2-day truck freight from Toronto covers NYC, Westchester, Hudson Valley and Long Island. NYC DOB and FDNY accept the UL certificate on UVB-G310. See Fire Protection New York.

Boston. 2-day truck freight from Toronto covers Boston, Cambridge, the North Shore, South Shore and MetroWest. 780 CMR and BFD acceptance under UL listing. See Fire Protection Boston.

London UK. UK partner warehouse stocks UVB-G310 for 48-hour delivery to central London. Toronto HQ ships non-stock sizes on 5 to 7 day air freight via Heathrow. See Fire Protection London.

Related products for complete sprinkler zone protection

UVB-G310 butterfly valves install on a zone that also includes alarm valve, gate valve isolation, grooved couplings and test-and-drain station. ValveAtlas stocks the complete scope.

Alarm valves. UVW-1511-300 wet alarm valve, UVD-2511-300 dry pipe valve, UVPR-5311-300 pre-action valve, UVPPD deluge valve. See Wet Alarm Valves.

Gate valves. UV0199 OS&Y gate flanged, UV0299 NRS gate. Listed UL/ULC/FM for fire protection indicating valve service upstream of the butterfly valve in branch configuration.

Grooved couplings and fittings. UV11 rigid 300 psi CWP, UV14 flexible 300 psi CWP, UV15 heavy-duty rigid 500 psi CWP, UV16 heavy-duty flexible 500 psi CWP. See Coupling Fittings pillar page.

Post indicator valves. UV0800-IP post indicator valve for private water main isolation at the property line on campus and industrial sites.

Test and drain. Listed 2-way test and drain stations at the sprinkler zone inspector’s test. See Test and Drain Valves.

Frequently asked questions

What is the difference between a grooved, wafer and lug butterfly valve? Grooved (UVB-G310) connects to grooved-end pipe via the UV11 or UV14 coupling and is the default on sprinkler risers. Wafer (UVB-W310) installs pin-between-flange between two flanges and is used where flanged pipe is already in service. Lug (UVB-L310) has threaded lugs allowing downstream removal without draining upstream pressure; used on fire pump discharge headers and at zone control where one side of the valve may need to be removed while the other stays pressurized.

Is the tamper switch integrated or separate? UVB-G310, UVB-W310 and UVB-L310 ship with factory-integrated SPDT tamper switch terminated at a junction box on the gear operator housing. The switch monitors valve position; closure of the valve triggers a supervisory signal at the fire alarm control panel per NFPA 72 and BS EN 12845.

What is the minimum and maximum size? UVB-G310 ranges 2″ through 12″ in grooved-end configuration covering standard sprinkler zone service. Larger sizes (14″, 16″, 18″, 20″, 24″) are available on 4 to 6 week special order for fire pump discharge mains and underground water main isolation.

Is UVB-G310 accepted on high-rise fire pump discharge at 500 psi? Standard UVB-G310 is rated 300 psi CWP. For fire pump discharge operating at 500 psi on tall high-rise buildings, ValveAtlas coordinates the 500 psi-class heavy-duty butterfly valve variant. Specify the pressure class on the purchase order and ValveAtlas will confirm stock position or factory lead time.

What temperature rating does UVB-G310 carry? Standard operating temperature is -10°C to +110°C (14°F to 230°F). Below -10°C, coordinate with ValveAtlas for low-temperature elastomer seat options. For hot-water fire protection service on foam systems above 110°C, coordinate the EPDM high-temp or PTFE seat variant.

Contact ValveAtlas for a butterfly valve quotation

For butterfly valve quotations and approved-equal submittal packages on Toronto, Montreal, New York, Boston or London projects, email the project specification and drawings to info@valve-atlas.com or use the contact form on our website. Standard turnaround is 48 hours from receipt of the project specification.