Hydrants Boston

Hydrants Boston: UL 246 Listed and FM 1510/1511 Approved AWWA C502 Dry-Barrel and AWWA C503 Wet-Barrel Fire Hydrants for 780 CMR, 527 CMR 1.00, AWWA C502 and NFPA 24 Municipal Fire Mains, Private Fire Service and Industrial Fire Water

ValveAtlas supplies UL 246 Listed, FM Class 1510/1511 Approved and AWWA C502 (dry-barrel) and AWWA C503 (wet-barrel) fire hydrants including compression-type dry-barrel, wet-barrel, monitor (wall) hydrants and yard/industrial hydrants to fire protection contractors, civil underground contractors, municipalities and industrial facility owners across Boston, Cambridge, Somerville, Quincy, Brookline, Newton, Waltham, Worcester and Springfield. Metro delivery, ductile-iron hydrant bodies with epoxy-lined interior, bronze operating mechanism, stainless hardware and safety break-flange for traffic collision protection designed for New England frostline 4 ft to 5 ft (1.2 m to 1.5 m), White Mountains 6 ft (1.8 m) service and 780 CMR submittal packages for BFD.

This page is the technical reference for Boston specifying engineers, civil underground contractors, fire protection engineers and municipal water utilities selecting fire hydrant packages for airport airside distribution, defense, aerospace, marine terminal and LNG industrial sites, Boston, Cambridge, Newton and Worcester municipal fire-main distribution, university campuses, colocation data centers and any NFPA 24 private fire service main or municipal fire hydrant installation, governed by 780 CMR (Massachusetts State Building Code), 527 CMR 1.00, NFPA 24 and AWWA C502 dry-barrel.

Hydrant range for Boston fire protection projects

Type SKU Main valve opening (MVO) Max working pressure Listings Typical Boston application
Dry-barrel compression type UVH-3DRY-5.25 5.25 inch MVO 250 psi UL 246, FM 1510, AWWA C502 Municipal fire main with freeze-drain for Canadian and Northern US installations
Dry-barrel compression type UVH-3DRY-6.0 6 inch MVO high-flow 250 psi UL 246, FM 1510, AWWA C502 High-flow hydrant for industrial and airport apron
Wet-barrel monitor type UVH-5BR-4.5 4.5 inch MVO 250 psi UL 246, FM 1511, AWWA C503 Indoor parking garage monitor hydrant, heated enclosure outdoor
Dry-barrel with Storz connection UVH-3DRY-STZ4 5.25 inch MVO, Storz 4 inch pumper 250 psi UL 246, FM 1510, AWWA C502 Quick-connect hydrant for rapid deployment fire department apparatus
High-pressure dry-barrel UVH-3DRY-HP 5.25 inch MVO 350 psi UL 246, FM 1510, AWWA C502 High-pressure fire loop for industrial and high-rise lead-in
Yard or industrial hydrant UVH-YARD-2.5 2.5 inch yard single-nozzle 250 psi UL 246, FM 1510 Small industrial site with single 2.5 inch nozzle
Break-flange traffic model UVH-3DRY-BF 5.25 inch MVO with break-flange 250 psi UL 246, FM 1510, AWWA C502 Curbside or apron with vehicle collision protection, break-safe flange
Flush-type ground hydrant UVH-FLUSH-6 6 inch ANSI flange 250 psi UL 246, FM 1510, AWWA C502 Flush ground hydrant for airport apron or parking deck
Wall or monitor-style UVH-WALL-2.5 2.5 inch wall-mount 250 psi UL 246, FM 1510 Industrial building wall-mount monitor hydrant, fire brigade connection

Why Boston contractors choose ValveAtlas hydrants

UL 246 and FM 1510/1511 dual listing for BFD acceptance. Every hydrant we supply is UL 246 Listed (hydrants for fire-protection service) and FM Class 1510 (dry-barrel) or 1511 (wet-barrel) Approved. BFD accepts listed hydrants with factory submittal, 780 CMR compliance letter and NFPA 24 private fire service main documentation and AWWA C502 dry-barrel compliance certificate.

Dry-barrel compression type for freeze protection. UVH-3DRY series compression-type dry-barrel hydrants with main valve at the inlet base, automatic bottom drain opens when the hydrant is closed, and a dry barrel above the main valve prevents freeze damage. Critical for Boston installations in New England frostline 4 ft to 5 ft (1.2 m to 1.5 m), White Mountains 6 ft (1.8 m). Standard bury depths 4 ft, 4.5 ft, 5 ft, 5.5 ft and 6 ft match local frostline requirements.

Wet-barrel monitor type for heated enclosures. UVH-5BR wet-barrel hydrants with integral nozzle valves on the barrel allow independent nozzle operation without closing the main. AWWA C503 listed; used for indoor parking garage monitors, heated enclosures, tropical exposures or below-frostline positive-drain municipal systems. Not recommended for freeze-exposed installations in Boston without heat trace.

Ductile iron with fusion-bonded epoxy. UVH bodies are ductile iron ASTM A536 Grade 65-45-12 with factory fusion-bonded epoxy interior and exterior coating per AWWA C550. Bronze seat, bronze operating nut, stainless steel stem and EPDM seal. 250 psi standard working pressure with 500 psi hydrostatic test per AWWA C502.

Safety break-flange for traffic protection. UVH-3DRY-BF break-flange (or “traffic model”) hydrants include an engineered shear zone at the ground-line barrel so that a vehicle collision shears the upper barrel without damaging the buried main valve or supply main. Allows quick field replacement of the upper barrel without excavation. AWWA C502 compliant.

Nozzle configuration customized to BFD. Standard Boston nozzle configuration is one 4.5 inch NH (Steamer) with National Standard Thread and two 2.5 inch NH, with thread form matching local fire department apparatus hose couplings. Storz 4 inch or 5 inch quick-connect common for BFD and surrounding mutual-aid. Pentagon-head operating nut sized to BFD fire service wrench (typically 1-1/2 inch or 1-1/4 inch pentagon).

Code and listing acceptance for Boston

780 CMR (Massachusetts State Building Code). 780 CMR (Massachusetts State Building Code) references NFPA 24, 527 CMR 1.00 and AWWA C502 dry-barrel for private fire service main hydrants. Hydrant spacing and coverage are governed by NFPA 1 Fire Code and local fire flow requirements. Municipal hydrants follow AWWA M17 Maintenance and NFPA 291 Flow Testing. The UVH series ships 780 CMR compliant.

NFPA 24 private fire service main hydrant. NFPA 24 specifies listed hydrant on private fire service main with indicating control valve (post indicator valve or wall indicator valve) upstream to allow isolation without main shutdown. UVH series satisfies NFPA 24 requirement for listed hydrants on private mains serving warehouses, industrial sites, campuses and data centers.

AWWA C502 dry-barrel hydrant. AWWA C502 governs dry-barrel hydrants with 3-inch to 6-inch MVO, compression-type main valve, and freeze-drain design. UVH-3DRY series meets AWWA C502 with 5.25 inch MVO standard, 6 inch high-flow option and 250 psi working pressure with 500 psi test. AWWA C502 also covers traffic break-flange provisions.

AWWA C503 wet-barrel hydrant. AWWA C503 governs wet-barrel hydrants for non-freeze climates with one main valve per nozzle. UVH-5BR series meets AWWA C503 for indoor monitor, heated enclosure and freeze-immune installations. Not appropriate for most Boston exterior applications without heat trace.

NFPA 291 flow testing. NFPA 291 governs fire flow testing of hydrants at residual and static pressure to validate hydrant color-coding (blue 1500 gpm and up, green 1000 gpm, orange 500 gpm, red under 500 gpm). All UVH hydrants ship unpainted body with customer-specified cap color per BFD standard color code.

BFD acceptance. Boston Fire Department (BFD), MA Board of Fire Prevention Regulations and MWRA inspection references 780 CMR (Massachusetts State Building Code), 527 CMR 1.00, NFPA 24, AWWA C502 dry-barrel and manufacturer listing. Factory submittal with UL/FM/AWWA certificates, municipal acceptance test and hydrostatic test per AWWA C502 required for sign-off.

Approved-equal submittals

Where a specification names a specific manufacturer, we prepare an approved-equal submittal package (listing certificates, dimensional drawings and material data) for review by the engineer of record and the authority having jurisdiction.

Installation scenarios for Boston hydrants

Airport airside distribution and apron hydrants. Airport fire main with UVH-3DRY-5.25 standard dry-barrel at terminal gates, UVH-FLUSH-6 flush ground hydrants on apron and taxiway perimeter for crash fire rescue (CFR) access, and UVH-3DRY-BF break-flange at vehicle-exposed curbs. Hydrant spacing with 250 ft coverage per hydrant on airside.

Defense, aerospace, marine terminal and LNG industrial fire water and process safety. Industrial site private fire main with UVH-3DRY-6.0 high-flow hydrants for monitor tower refill, UVH-WALL-2.5 wall-mount hydrants on building face for brigade connection, and UVH-3DRY-HP 350 psi high-pressure on foam suppression header. NFPA 24 compliant with listed control valves upstream.

Boston, Cambridge, Newton and Worcester municipal fire main distribution. Municipal street hydrants with UVH-3DRY-5.25 standard 5.25 inch MVO at 300 ft to 500 ft spacing per ISO fire flow requirements. Break-flange option UVH-3DRY-BF for curbside and intersection placements. AWWA M17 maintenance and NFPA 291 flow testing compliant.

University campus and colocation data center. Campus and data center private fire loop with UVH-3DRY-5.25 at 300 ft spacing, UVH-3DRY-HP 350 psi near fire pump discharge and UVH-WALL-2.5 wall-mount at building face for fire brigade connection. NFPA 24 compliant with Post Indicator Valve (PIV) isolation upstream of each hydrant.

High-rise standpipe and fire pump room. Boston high-rise buildings with UVH-3DRY-5.25 at primary ingress and UVH-WALL-2.5 wall-mount in mechanical yards serving fire pump room test header. Supports fire pump flow test per NFPA 25.

Related products for complete Boston fire protection valve package

Gate valves. UVG-OSY OS&Y rising stem gate valves and UVG-NRS non-rising-stem post indicator valves upstream of hydrant per NFPA 24. See Gate Valves Boston.

Post indicator valves. UVPIV-BG post indicator valves as the indicating control valve on hydrant isolation per NFPA 24. See Post Indicator Valves Boston.

Fire pumps. UVFP-HSC, UVFP-ES and UVFP-VIL fire pumps feeding the hydrant loop per NFPA 20. See Fire Pumps Boston.

Check valves. UVC-NR silent-closure and UVC-SW swing check valves for fire pump discharge and sprinkler water supply per NFPA 13. See Check Valves Boston.

Frequently asked questions (Boston)

Are these hydrants accepted by BFD? Yes. These hydrants are UL 246 Listed, FM 1510/1511 Approved and AWWA C502 (dry-barrel) or AWWA C503 (wet-barrel) compliant. BFD accepts listed hydrants with factory submittal, 780 CMR compliance letter, NFPA 24 documentation and municipal water authority acceptance.

Dry-barrel vs wet-barrel for Boston? Dry-barrel is the default for Boston given New England frostline 4 ft to 5 ft (1.2 m to 1.5 m), White Mountains 6 ft (1.8 m). Wet-barrel is only appropriate for heated enclosures, indoor parking garage monitor hydrants or heat-traced installations. UVH-3DRY is the standard specification for outdoor Boston municipal and private fire main service.

What bury depth do I specify? Bury depth matches local frostline. Boston standard bury depths are 4 ft, 4.5 ft, 5 ft, 5.5 ft and 6 ft. Municipal water authority or engineer-of-record determines exact bury depth from soil survey. Hydrant comes with fixed bury; no field adjustment.

What nozzle configuration? Standard Boston configuration is one 4.5 inch NH (Steamer) with National Standard Thread and two 2.5 inch NH. Storz 4 inch or 5 inch quick-connect common for BFD and surrounding mutual-aid. Pentagon-head operating nut sized per BFD fire service wrench. Thread specified per factory order to match fire department couplings.

What is the pressure rating? Standard UVH-3DRY is 250 psi working pressure with 500 psi hydrostatic test per AWWA C502. UVH-3DRY-HP high-pressure option is 350 psi working pressure for industrial high-pressure loops and high-rise lead-ins. UVH-5BR wet-barrel is 250 psi AWWA C503.

What is the delivery time to Boston? Stock UVH-3DRY-5.25 at standard bury depths ships 2 to 4 weeks. Break-flange UVH-3DRY-BF and high-pressure UVH-3DRY-HP factory-built 4 to 6 weeks. Custom nozzle threads and Storz options 6 to 8 weeks. Metro freight from Toronto HQ 3 to 5 business days.

Contact ValveAtlas for Boston hydrant quotation

For hydrant quotations, approved-equal submittals for BFD approval, or NFPA 24 hydrant packages with AWWA C502 dry-barrel freeze protection for airport airside, Boston municipal main, industrial site, university campus, data center or high-rise lead-in projects, email the project civil drawings, bury depth, nozzle configuration and fire flow requirement to info@valve-atlas.com or use the contact form. Same-day response on Boston urgent orders.

Why ValveAtlas serves Greater Boston

We supply Massachusetts contractors with UL listed and FM approved valves and components for NFPA 13 systems under the Massachusetts State Building Code (780 CMR). Cross-border shipping from our Toronto warehouse via bonded freight to all New England states; typical Boston-area lead time is 4–6 business days depending on customs clearance.